TESCOM DX Series
DX Series
The new DX Power UPS series offers better power protection for critical infrastructure in commercial and industrial environments. The modern UPS architecture, incorporating three independent DSP circuits combined with a 3-level rectifier/inverter topology, low total harmonic distortion (THDi) and power factor = 1 on DX models & power factor = 0.9 on DXL models, is ideal for installations requiring superior performance. The units can be used as a single, stand-alone UPS or as a multi-chamber UPS system with up to 8 units connected in parallel, achieving a total power capacity of up to 3.2 MW.
- Real Online UPS topology without conversion
- Power Factor=1.0
- 3 separate DSPs for PFC rectifier, inverter and panel function control
- Overheat protection with 3 separate sensors
- 4 alarms for dry contact output relays (+8 optional output relays)
- Advanced remote control
- SNMP and MODBUS adapters (optional)
- Eco mode (optional)
MODEL DX3100 DX3120 DX3160 DX3200 DX3250 DX3300 DX3400 Power (kVA) 100 120 160 200 250 300 400 INPUT Voltage 380/400 VAC 3P + N + G ± 20% (100% load) / – 40% (70% load) Frequency 50Hz / 60Hz, ± 5% Power Factor ≥ 0.99 THDI ≤ 3% By-pass Voltage 380/400 VAC 3P + N, ± 10% (adjustable) Voltage Distortion ≤ 10% Protections Fuses, Voltage & Frequency tolerance, Input power limit, Phase sequence indicator OUTPUT Power (kW) 100 120 160 200 250 300 400 Power Factor 1 Voltage 380/400 VAC 3P + N, ± 1% (415 VAC optional) Frequency 50Hz / 60Hz Frequency Tolerance Line synchronized: ± 2% (adjustable) / Free running: ± 0.1% Efficiency Up to 95.5% Up to 96% Crest Factor 3:01 Overload Protection 100%–125% load: 10 min / 125%–150%: 1 min / >150%: by-pass Voltage THD ≤ 2% (100% linear load) Protections Advanced short circuit, Voltage tolerance, DC balance, Current limiting BATTERIES Type VRLA AGM / GEL / NiCd Nominal Voltage ± 360 VDC Float/Discharge ± 405 VDC / ± 300 VDC Battery Cabinet External Ambient Temp. 25ºC Protections 3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional) Auto Testing Standard every 72 hours (adjustable) GENERAL Standards EN62040-1, EN62040-2, EN62040-3 Interface TFT touch panel, 5 vector buttons, Buzzer Indicators Voltage, Current, Power, Crest Factor, Frequency, PF, Service Time Communication 2xRS232, 4 standard + 8 optional DRY contacts, EPO, Genset input Software T-Mon UPS Management Software (3 clients + 1 server) Protection Degree IP20 Noise <62 dBA <65 dBA <67 dBA Weight (kg) 210 220 262 270 440 575 655 Dimensions (mm) 1440x475x890 1900x880x775 1900x1250x775 OPTIONS Transformer Galvanic isolation transformer (external) Adaptors SNMP, RS485, MODBUS (RS485/TCP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem Parallel Operation Up to 8 units