TESCOM DX Series

DX Series

The new DX Power UPS series offers better power protection for critical infrastructure in commercial and industrial environments. The modern UPS architecture, incorporating three independent DSP circuits combined with a 3-level rectifier/inverter topology, low total harmonic distortion (THDi) and power factor = 1 on DX models & power factor = 0.9 on DXL models, is ideal for installations requiring superior performance. The units can be used as a single, stand-alone UPS or as a multi-chamber UPS system with up to 8 units connected in parallel, achieving a total power capacity of up to 3.2 MW.

  • Real Online UPS topology without conversion
  • Power Factor=1.0
  • 3 separate DSPs for PFC rectifier, inverter and panel function control
  • Overheat protection with 3 separate sensors
  • 4 alarms for dry contact output relays (+8 optional output relays)
  • Advanced remote control
  • SNMP and MODBUS adapters (optional)
  • Eco mode (optional)
    MODELDX3100DX3120DX3160DX3200DX3250DX3300DX3400
    Power (kVA)100120160200250300400
    INPUT
    Voltage380/400 VAC 3P + N + G ± 20% (100% load) / – 40% (70% load)
    Frequency50Hz / 60Hz, ± 5%
    Power Factor≥ 0.99
    THDI≤ 3%
    By-pass Voltage380/400 VAC 3P + N, ± 10% (adjustable)
    Voltage Distortion≤ 10%
    ProtectionsFuses, Voltage & Frequency tolerance, Input power limit, Phase sequence indicator
    OUTPUT
    Power (kW)100120160200250300400
    Power Factor1
    Voltage380/400 VAC 3P + N, ± 1% (415 VAC optional)
    Frequency50Hz / 60Hz
    Frequency ToleranceLine synchronized: ± 2% (adjustable) / Free running: ± 0.1%
    EfficiencyUp to 95.5%Up to 96%
    Crest Factor3:01
    Overload Protection100%–125% load: 10 min / 125%–150%: 1 min / >150%: by-pass
    Voltage THD≤ 2% (100% linear load)
    ProtectionsAdvanced short circuit, Voltage tolerance, DC balance, Current limiting
    BATTERIES
    TypeVRLA AGM / GEL / NiCd
    Nominal Voltage± 360 VDC
    Float/Discharge± 405 VDC / ± 300 VDC
    Battery CabinetExternal
    Ambient Temp.25ºC
    Protections3 level alarms, Battery fuses, Charging current limit, Temperature compensation (optional)
    Auto TestingStandard every 72 hours (adjustable)
    GENERAL
    StandardsEN62040-1, EN62040-2, EN62040-3
    InterfaceTFT touch panel, 5 vector buttons, Buzzer
    IndicatorsVoltage, Current, Power, Crest Factor, Frequency, PF, Service Time
    Communication2xRS232, 4 standard + 8 optional DRY contacts, EPO, Genset input
    SoftwareT-Mon UPS Management Software (3 clients + 1 server)
    Protection DegreeIP20
    Noise<62 dBA<65 dBA<67 dBA
    Weight (kg)210220262270440575655
    Dimensions (mm)1440x475x8901900x880x7751900x1250x775
    OPTIONS
    TransformerGalvanic isolation transformer (external)
    AdaptorsSNMP, RS485, MODBUS (RS485/TCP), USB Alarm Logger, TCP/IP, GSM/GPRS Modem
    Parallel OperationUp to 8 units